Performance of doubly fed induction generator (DFIG) during network faults
Authors: Anaya-Lara, O.; Wu, X.; Cartwright, P.; Ekanayake, J.B.; Jenkins, N.
Source: Wind Engineering, Volume 29, Number 1, January 2005 , pp. 49-66(18)
Publisher: Multi-Science Publishing Co Ltd
Key:
- Free Content
- New Content
- Subscribed Content
- Free Trial Content
Abstract:
This paper addresses the dynamic modelling of large (MW) capacity Doubly Fed Induction Generators (DFIG) wind turbines using Pscad/Emtdc and Matlab/Simulink. Suitable speed and reactive power controllers are implemented and described. Application studies are conducted to observe the performance of the DFIG during power system disturbances such as three-phase faults developing in different points of the network. These studies are used to determine the DFIG's fault current contribution and power converter rating required for fault ride-through capability and protection requirements. Simulations results are presented and discussed using typical turbine and network data for wind farm facilities.Document Type: Regular paper
DOI: 10.1260/0309524054353728
Key:
- Free Content
- New Content
- Subscribed Content
- Free Trial Content

Click here for Page Help